Basic video for instruction about relay configuration and using software can be access from below link:
Protection and Control Training Videos
---> Select Unlock Training Videos
---> Fill the form
---> Video list will be sent to email
1. GR100 (G1) series: GBU100, GRB100, GRD110, GRD140, GRL100, GRT100, GRZ100.
2. GRE100 (GRE or MV) series: GRE110, GRE120, GRE130, GRE140, GRE160, GRE170.
3. GR200 (G2) series: GBU200, GRB200, GRD200, GRL200, GRT200, GRZ200, GRH200.
4. GRE200 (New GRE) series: GRE200, GRW200.
1. GR-100 (G1) series: RS232 port (female), straight cable, baudrate 9600bps.
2. GRE100 (GRE or MV) series: USB-B port, A-B USB cable (cable for printer), baudrate 9600bps.
3. GR-200 (G2) series: USB-B port, A-B USB cable (cable for printer), baudrate 115.2kpbs or 921.6kbps.
4. GRE200 (New GRE) series: USB-B port, A-B USB cable (cable for printer), baudrate 921.6kbps.
1. GR100 (G1) series: The ordering code and S/N are on relay's front panel.
2. GRE100 (GRE hay MV) series: The odering code is on the left side of front panel and the S/N is on the right side of front panel (under a cover).
3. GR200 (G2) series: The ordering code and S/N are on the relay's left rear side, or accessing Main Menu/Information on LCD screen to show.
4. GRE200 (New GRE) series: The ordering code and S/N are on the relay's front panel, or accessing Main Menu/Information on LCD screen to show.
In order to change relay's IP address, need to write to relay both Setting and IEC-61850.
At Main screen, accessing Test → Test Mode → press Enter → select On → Enter → press Right key → Binary Output → Select slot BO → select BO needs closed (opened) → Select On (off) → move to top → Enter → press Enter will operate closing (opening) output
Need to use "Input dummy signal number" variables for PLC configurations
Apply to all GR-200 relays (G2 series with software code: 1,2)
Access here and download instruction manual for GR-200 G2 series (software code = 1,2) at section 6.
Due to one of these following reasons (use online debug in Multiprog to check):
- Wrong signal number (Q=0)
- Identical signal number (with input signal, Q=0)
- PLC has been stopping for a long enough time - Error code = 10 (Need action "Cold"). This could be caused by Stop PLC action or PLC automatically stop by overload configuration.
- This is a feature of relay.
- Time saved by relay according to UTC (Universal Time Coordinated)
- Time displaying in GR-TIEMS depends on computer's time zone.
- Probably third party softwares do not include computer's time zone
- Record's name is automatically generated based on UTC
Use signal PLC_Group_ENUM (DOUT_UINT) to change group settings
Download PLC file here
Apply to all GR-200 relays (G2A series with software code = 3)
Note: Use Edition 1 Option or Edition 2 for IEC-61850
Refer to section in manual file: Recording function → Transferred information during fault → Transferred metering values
GBU200: Section 7.4.1
GRD200: Section 8.4.1
GRB200: Section 7.4.1
GRL200: Section 8.4.1
GRT200: Section 9.4.1
GRZ200: Section 8.4.1
Setting based on connection structure between 2 relays GRL200
Please check instruction file here
Only use "Vendor" account to write Replica configuration. Then use "Full Access" account for other settings
Download instruction file here
Refer to section General Control function → LED Reset function (LEDR) to edit Logical Node
GBU200: Section 2.13
GRD200: Section 3.6
GRB200: Section 3.6
GRL200: Section 3.6
GRT200: Section 4.4
GRZ200: Section 3.6
This is instruction for changing the rated current from 1A to 5A and vice versa for GR-200 series. Download instruction file here.
Note: for GRE100 series users can change the rated current 1A/5A by setting in RSM100.
Software Switch (SOFTSW) Configuration Guidance for GR-200 Series can be downloaded here
Instruction for GR-200 series signal monitoring using GR-TIEMS can be downloaded here