Operational support

1. GR100 (G1) series: GBU100, GRB100, GRD110, GRD140, GRL100, GRT100, GRZ100.
2. GRE100 (GRE or MV) series: GRE110, GRE120, GRE130, GRE140, GRE160, GRE170.
3. GR200 (G2) series: GBU200, GRB200, GRD200, GRL200, GRT200, GRZ200, GRH200.
4. GRE200 (New GRE) series: GRE200, GRW200.

1. GR-100 (G1) series: RS232 port (female), straight cable, baudrate 9600bps.

2. GRE100 (GRE or MV) series: USB-B port, A-B USB cable (cable for printer), baudrate 9600bps.

3. GR-200 (G2) series: USB-B port, A-B USB cable (cable for printer), baudrate 115.2kpbs or  921.6kbps.

4. GRE200 (New GRE) series: USB-B port, A-B USB cable (cable for printer), baudrate 921.6kbps.

1. GR100 (G1) series: The ordering code and S/N are on relay's front panel.

2. GRE100 (GRE hay MV) series: The odering code is on the left side of front panel and the S/N is on the right side of front panel (under a cover).

3. GR200 (G2) series: The ordering code and S/N are on the relay's left rear side, or accessing Main Menu/Information on LCD screen to show.

4. GRE200 (New GRE) series: The ordering code and S/N are on the relay's front panel, or accessing Main Menu/Information on LCD screen to show.

At Main screen of relay, Accessing Time → Clock → ActiveSyncSrc (Time source of relay):

- Local Indicator: relay is not synchronized with any source.

- Other Indicator: protocol which relay is synchronized with. Pressing Right key: star mark will be at the current time source of relay.

When Error LED On, user can check error information with following methods:

- Method 1: Pressing funtion key F6, then press Right key ► for detailed information.

- Method 2: At Main screen, accessing Monitoring → Diagnostic, then press Right key ► for detailed information.

Pressing MENU/MIMIC button on relay's front panel

At Main screen of relay, accessing Monitoring → Binary I/O → select the necessary slot:

- Binary Input: status "1" means high active, status "0" means low active;

- Binary Output: status "1" means BO is closing, status "0" means BO is opening

At GR-TIEMS, accessing Tool → Label Creator

- Print Contents: select LED, Single (for 01 relay) or Multi (several relays).

- Paper: Regular/Other Page

- Font size: 7.5 or 8.

- Target IEDs: select IED

- Select Preview to confirm before printing

Refer to instruction manual, files need to be stored in 1 folder:
- Disturbance record
- Fault record
- Event record

Two methods to check measurement parameters:
- Method 1: Press F1
- Method 2: On relay's screen, access Monitoring → Metering

On relay's screen, access to Monitoring → Communication → Port Status:
- Up: Port is connected
- Down: Port is not connected

Download GSC1000-C operational instruction manual here

Instruction for connection with GR-200 series relays using Multi-Prog.

Please check instruction here.